True E6 on an ice machine: head pressure climbed too high

The control watches the pressure leaving the compressor and raises E6 once it goes above 370 psi.

(844) 410-9163

Mon–Sat, 8am–8pm

  • Condenser and airflow
  • Ice machine condenser and fan repair
  • Source: True Residential

Book a visit

Three short steps, about a minute.

or call (844) 410-9163

What E6
actually means.

The control watches the pressure leaving the compressor and raises E6 once it goes above 370 psi. On an air-cooled True head that almost always means the condenser is not shedding heat, because of a clogged air filter, a dirty coil or a fan that is not turning.

True Residential ice machine display

What to do when E6 shows on the ice machine

Before you book,
in this order.

Each step comes from True Residential's own guidance for E6 on its ice machines. Follow it to the end: the last card says whether this is a visit.

01

Turn the head off at the touchscreen and slide out the air filter; wash it in warm water with a neutral cleaner and let it dry before refitting.

02

Clear boxes, bags or stored stock away from the air intake and outlet so the head can breathe.

03

Restart ice making and watch for the condenser fan to turn; if it does not, or E6 comes back, book a visit for the coil and the fan motor.

Still there?

It usually turns into ice machine condenser and fan repair. Book with the code and the model number.

What not to do

E6 reads the pressure itself, while E20 is the separate high-pressure limit on the HP1 transducer and E7 means that transducer lost its signal. A hot room can push pressure up too, which is why E14 for high ambient temperature often appears alongside it.

Where E6 usually leads

Ice machine condenser and fan repair.

Condenser cleaning, fan motor, water regulating valve or remote condenser work · low to moderate.

In True Residential's own words

Discharge pressure has exceeded 370 psi
True Ice TCIM modular ice machine service manual (TEC_TM_198 Rev A) True Ice TCIM modular ice machine service manual (TEC_TM_198 Rev A)

Every code on this site is taken from the manufacturer's documentation, never from a forum or a parts listing. True Ice TCIM air-cooled modular heads (TCIM-422 to TCIM-830), touchscreen control; the code shows on the active alarm screen and stays in the alarm log.

True Residential E6 ice machine repair,
where we come out.

The same visit in every metro below: the code, the model number, and a diagnosis before any part is ordered.

All service areas
A family filling glasses with nugget ice from an ice machine in a large home kitchen.
For the heart of your home.

Questions
about E6.

Can I clear E6 myself?
Turn the head off at the touchscreen and slide out the air filter; wash it in warm water with a neutral cleaner and let it dry before refitting. If it comes back, it needs a visit.
Can I clean the condenser coil on a True ice machine myself?
The air filter is yours to wash, monthly per True's schedule. A coil that is caked with grease needs chemical cleaning, which True leaves to a service professional.
Why did E6 show up on my True ice machine in summer?
Warmer room air and a filter that has been collecting dust all season both raise head pressure. Cleaning the filter usually clears it, and a repeat in hot weather points at the coil or fan.
Will E6 damage my True compressor?
The alarm exists to stop the machine before high pressure does harm. Running repeatedly into it is what wears a compressor, so a code that keeps returning deserves a visit.